The Modbus-Square D PowerLogic Ethernet OPC Server communicates
with one or more Modicon TCP/IP Ethernet PLC(s) and/or devices connected
to one or more Square D POWERLOGIC Ethernet Communication Modules (ECM) or
Ethernet Communication Cards (ECC) using MODBUS/TCP as the application protocol
over an Ethernet network.
Device redundancy is built into the server. It can be configured to provide
complete, automatic switch over to backup controllers on failure detection or
under application control. Device redundancy provides uninterrupted data
transfer between the process and the client application(s).
The Modbus-Square D PowerLogic Ethernet OPC Server
supports data exchange with Clients via Microsoft's Object Linking and
Embedding (OLE) for Process Control (OPC). This Server meets the OPC Data
Server Specification Version 2.0. It also supports OPC Version 1.0.
The Server has a graphical user interface (GUI) configuration environment
with an "Explorer" look and feel. The configuration environment allows
the Server to be configured with information such as which device to interface
with and which data in those configured devices should be accessed. Once
data points have been configured, the Server can communicate with these
devices on behalf of the Clients. Data exchanged occurs between the Server
and the defined device data locations. These locations are defined
as part of the configuration process generating Tags in the Server database.
Clients and the Server then reference the data via the tag names.
The Server was developed by DASTEC Corporation using the OPC Server
Toolkit from FactorySoft, Inc.
Specifications
Operating System Supported: Windows 95/98/NT/2000 and newer.
Protocol Supported: MODBUS/TCP protocol over TCP/IP Ethernet.
Write General Reference (XREGs) (function code 21)
Mask Write Register (HREG) (function code 22)
Read FIFO Queue (function code 24)
Device Supported: Any controller or device supporting the above protocol and one or
more of the listed function codes can be used
with the Server. These include Modicon PLCs, Square D Ethernet Communication
Modules (ECM) and Square D Ethernet Communication Cards (ECC).
Data Types Supported: COIL, DINP, HREG, IREG, LREG, FREG, DREG, XREG, EXSTAT and FIFO
Data Scaling and Formats Supported: INT, UINT, LONG, ULONG, FLOAT, MODFLT (Modbus Float),
DOUBLE, STRING, RSTRING (reverse string), PowerLogic 3 register DATETIME,
PowerLogic PF (power factor), PowerLogic Scale Factors A-F and fixed decimal position scaling.